Power cables for general applications in construction works subjet to reaction to fire requirements, PVC insulated (S18), PVC sheated (R18), with special requirements of reaction to fire performance according to the Construction Products Regulation (CPR) Cables with flexible conductors without screen
Rated Voltage U0/U : 450/750 V
Class of reaction to the performance : Cca-s3-d1-a3
Compliant with the requirements of the BT 2014/35/UE directives
CEI EN 50575:2014 + 50575/A1:2016 power cables
Cables for general applications in construction works subject to reaction to fire requirements
CEI EN 60228 CEI 20-29 IEC 228 conductor of isolated cables
CEI EN 50363 CEI 20-11/0-1;V1 physical characteristic
CEI EN 50399 common test methods for cables under fire conditions
CEI EN 60332-1-2 test for resistance to vertical flame propagation for a single insulated conductor or cable
CEI EN 60754-2 tests on gases evolved during combustion of materials from cables
Determination of acidity (by pH measurement)
CEI UNEL 00722 identification of cores in cables
CEI UNEL 35016 class of reaction to fire of the cables in relation to the EU “Construction Products Regulations” (305/2011)
Nominal voltage Uo/U : 450/750 V
Testing voltage : 2000 V
Max. working temperature : 70°C
Max. short circuit temperature : 160°C
Cable for fixed installation
Bending radius minimum : 4 times outer diameter of cable
Tensile stress : 50 N for mm² of copper cross section
Min. laying temperature : 0°C
BROWN RAL 8003
Red Cavi spa FS18OR18 450/750 V (n° of conductors of rated cross section) Cca-s3,d1,a3 IEMMEQU EFP (metric) batch