FG16OR16 (CE)

Control and signalling cables, HEPR insulated (G16), PVC sheathed (R16), with special requirements of reaction to fire performance according to the Construction Products Regulation (CPR) UE 305/11
Multicore cables with flexble conductors for fixed installation
Rated voltages U0/U : 0,6/1 kV
Class of reaction to the performance : Cca-s3,d1,a3

Compliant with the requirements of the BT 2014/35/UE directives

Reference rules

CEI 20-13:2011 rubber insulated cables with rater voltages between 1 kV and 30 kV 

CEI EN 60228 CEI 20-29 IEC 228 conductor of isolated cables

CEI EN 50363 CEI 20-11/0-1;V1 physical characteristic

CEI EN 50399 common test methods for cables under fire conditions

CEI EN 60332-1-2 test for resistance to vertical flame propagation for a single insulated conductor or cable

CEI EN 60754-2 tests on gases evolved during combustion of materials from cables

Determination of acidity (by pH measurement)

CEI UNEL 00722 identification of cores in cables

CEI UNEL 35318 power cables 06/1 Kv

CEI UNEL 35016 class of reaction to fire of the cables in relation to the EU “Construction Products Regulations” (305/2011)

Electric characteristics

Nominal voltage Uo/U : 0,6/1 kV

Testing voltage : 4000 V

Max. working temperature : 90°C  

Max. short circuit temperature : 250°C

Installation conditions

Cable for fixed installation

Bending radius minimum : 6 times outer diameter of cable

Tensile stress : 50 N for mm² of copper cross section

Min. laying temperature : 0°C

Sheath color

Grey RAL 7035

Marking

Red Cavi FG16OR16 0,6/1 kV (n. of conductors of rated cross section) Cca-s3,d1,a3 IEMMEQU EFP (metric) batch