Control and signalling cables, HEPR insulated (G16), PVC sheathed (R16), with special requirements of reaction to fire performance according to the Construction Products Regulation (CPR) UE 305/11
Multicore cables with flexible conductors for fixed installation,with braid screen copper
Multicore cables with flexble conductors for fixed installation
Rated voltages U0/U : 0,6/1 kV
Class of reaction to the performance : Cca-s3,d1,a3
Compliant with the requirements of the BT 2014/35/UE directives
CEI 20-13:2011 rubber insulated cables with rater voltages between 1 kV and 30 kV
CEI EN 60228 CEI 20-29 IEC 228 conductor of isolated cables
CEI EN 50363 CEI 20-11/0-1;V1 physical characteristic
CEI EN 50399 common test methods for cables under fire conditions
CEI EN 60332-1-2 test for resistance to vertical flame propagation for a single insulated conductor or cable
CEI EN 60754-2 tests on gases evolved during combustion of materials from cables
Determination of acidity (by pH measurement)
CEI UNEL 00722 identification of cores in cables
CEI UNEL 35318 power cables 0,6/1 kV
CEI UNEL 35016 class of reaction to fire of the cables in relation to the EU “Construction Products Regulations” (305/2011)
Nominal voltage Uo/U : 0,6/1 kV
Testing voltage : 4000 V
Max. working temperature : 90°C
Max. short circuit temperature : 250°C
Cable for fixed installation
Bending radius minimum : 4 times outer diameter of cable
Tensile stress : 50 N for mm² of copper cross section
Min. laying temperature : 0°C
Grey RAL 7035
Red Cavi FG16OH2R16 0,6/1 kV (n° of conductors of rated cross section) Cca-s3,d1,a3 (metric) batch