FS18OR18

Control and signalling cables for general applications in construction works subjet to reaction to fire requirements, PVC insulated (S18), PVC sheated (R18), with special requirements of reaction to fire performance according to the Construction Products Regulation (CPR) Cables with flexible conductors without screen
Rated Voltage U0/U : 300/500 V 
Class of reaction to the performance : Cca-s3-d1-a3

Compliant with the requirements of the BT 2014/35/UE directives

Reference rules

CEI EN 50575:2014 + 50575/A1:2016 power cables

Cables for general applications in construction works subject to reaction to fire requirements

CEI EN 60228 CEI 20-29 IEC 228 conductor of isolated cables

CEI EN 50363 CEI 20-11/0-1;V1 physical characteristic

CEI EN 50399 common test methods for cables under fire conditions

CEI EN 60332-1-2 test for resistance to vertical flame propagation for a single insulated conductor or cable

CEI EN 60754-2 tests on gases evolved during combustion of materials from cables

Determination of acidity (by pH measurement)

CEI UNEL 00722 identification of cores in cables

CEI UNEL 35016 class of reaction to fire of the cables in relation to the EU “Construction Products Regulations” (305/2011)

Electric characteristics

Nominal voltage Uo/U : 300/500 V

Testing voltage : 2000 V

Max. working temperature : 70°C

Max. short circuit temperature : 160°C

Installation conditions

Cable for fixed installation

Bending radius minimum : 4 times outer diameter of cable

Tensile stress : 50 N for mm² of copper cross section

Min. laying temperature : 0°C

Sheath color

BROWN RAL 8003

Marking

Red Cavi FS18OR18 300/500 V (n° of conductors of rated cross section) Cca-s3,d1,a3 IEMMEQU EFP (metric) batch